| Description
|
|
|
| Features |
• Universal Full range AC input
• Installed on DIN Rail TS35/7.5 or 15
• Short circuit, Overload and Over Voltage protection
• Isolation Class II (C-DR-30/60/100-xx)
• UL 508 listed (C-DR-45xx)
• UL/CUL/TUV/CB/CE Approval
• No load power consumption <1W (C-DR-100-xx)
• LED indicator for power on
• Cooling by free air convection
• 100% full load burn-in test
• 3 years warranty
|
| Specifications |
| AC input voltage range |
88~264VAC; 124~370VDC |
| AC inrush current (Cold start) |
30A at 115VAC
45A at 230VAC |
DC adjustment range
(rated output Voltage) |
12V: 12~15V
15V: 15~18V
24V: 24~29V |
Overload protection (constant
current limiting, auto-recovery) |
105~135% |
Over Voltage protection
(rated output Voltage) |
125~155% |
Setup, rise, hold up time
(at full load and 230VAC) |
2700ms, 80ms, 50ms |
| Withstand voltage |
I/P-O/P: 3KVAC |
| Working Temperature |
-20~60¢XC
(refer to output derating curve) |
| Safety standards |
UL60950-1
TUV EN60950-1 approved |
| EMS standards |
EN55022 classB, ENV50204, EN61000-3-2,3, EN61000-6-2
EN61000-4-2,3,4,5,6,8,11, EN61204-3(except CP-DR-045xx) |
| Connection |
I/P: 2 poles
O/P: 4 poles
screw DIN terminal |
Packing
|
0.35Kg
36pcs/13.6Kg/1.1CUFT |
|
| Model |
Model No.
|
Output |
Tol. |
R&N |
Effi. |
| Power |
Voltage |
Current |
| C-DR-100-12 |
100W |
12V |
0~7.5A |
¡Ó1% |
120mV |
87% |
| C-DR-100-24 |
100W |
24V |
0~4.2A |
¡Ó1% |
150mV |
89% |
|
|