| Description
|
|
|
| Features |
• Battery controller for DIN rail UPS system
• Parallel connection to DC BUS
• Suitable for 24V system up to 40A
• Installed on DIN Rail TS35/7.5 or 15
• Built-in battery test function
• Battery polarity protection
• Relay contact signal output and LED indicator for DC BUS OK, Battery Fail and Battery Discharge
• Cooling by free air convection
• 3 years warranty
|
| Specifications |
| DC input / DC BUS |
24~29V, 40A max. |
| Battery input voltage |
21~29V |
| Battery input current |
0~40A |
| Chagre current (typ.) |
2A |
| External battery (typ.) |
24V, 4AH / 7AH / 12AH |
| DC BUS OK |
Relay status: Short when DC voltage between 21~29V(¡Ó3%), relay contacts
LED(green): DC BUS OK/NO: bright/dark |
| Battery fail |
Relay status: Short when battery fail is observed through the battery
test function, relay contacts
LED(red): Battery over-discharge warning or battery broken/OK: bright/dark |
| Battery discharge |
Relay status: Short when battery in discharge condition, relay contacts
LED(yellow): Battery discharge: bright, Battery is not discharging or
discharging current <1.5A: dark |
| Working Temperature |
-20~70¢XC |
| EMS standards |
EN55022 classB, ENV50204, EN61000-4-2,3,4,5,6,8 |
| Connection |
I/P: 2 poles, O/P: 2 poles screw DIN terminal, Signal output: 6 poles |
| Packing |
0.55Kg, 20pcs/12Kg/1.1CUFT |
|
| Model |
Model No.
|
DC BUS |
| Voltage |
Current |
| C-DR-UPS40 |
24~29V |
40A Max. |
|
|