FAQ ¢x Sitmap¢x Contact¢x About ¡@
 
 
¡@
     
     

Description

 

Features

• Universal Full range AC input
• Installed on DIN Rail TS35/7.5 or 15
• Short circuit, Overload and Over Voltage protection
• LED indicator for power on
• NES class 2 / LPS compliant (selected model)

• DC OK relay contact (C-MDR-40/60/100-xx)
• Cooling by free air convection
• 100% full load burn-in test
• 3 years warranty


Specifications


AC input voltage range 85~264VAC; 120~370VDC
AC inrush current (Cold start) 30A at 115VAC
60A at 230VAC
DC adjustment range
(rated output Voltage)
0~20%
Overload protection (constant
current limiting, auto-recovery)
105~150%
Over Voltage protection
(rated output Voltage)
125~150%
Setup, rise, hold up time 500ms, 30ms, 50ms at full load and 230VAC
Withstand voltage I/P-O/P: 3KVAC
I/P-FG: 1.5KVAC, 1 minute
Working Temperature -20~60¢XC@100%
70¢XC@60% load
DC OK Signal Relay contact
Safety standards UL 508, TUV EN60950-1 approved, NEC class 2 / LPS compliant*
EMS standards EN55022 classB, ENV50204, EN61000-3-2,-3, EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 heavy industry level (C-MDR-020xx excluded), EN61204-3
Connection I/P: 3 poles
O/P: 6 poles
screw DIN terminal
Dimensions(LxWxH) (mm) 40x90x100
Packing
0.3Kg
42pcs/13.6Kg/0.82CUFT
* Only for CP-MDR-020xx, CP-MDR-040-12/24, CP-MDR-060-12/24, CP-MDR-100-24


Model


Model No.
Output Tol. R&N Effi.
Power Voltage Current
C-MDR-40-5 40W 5V 0~6.00A ¡Ó2% 80mV 78%
C-MDR-40-12 40W 12V 0~3.33A ¡Ó1% 120mV 86%
C-MDR-40-24 40W 24V 0~1.70A ¡Ó1% 150mV 88%